Overload relay is the one of important device for motor control.It can prevent our motor from overheat or winding burning due overload of ampere.
We need to setting the value of overload relay properly depend on our application and motor full load ampere.If we setting low from FLA,it can cause motor trip c0ntinues and process not running smoothly.
But if we setting to high from FLA,the overload relay cannot protect the motor if overload happen.It can cause the motor failure or winding burns.So we must calculated and get a right setting for the overload relay.
How to setting Overload Relay protection?
Basically to setting the overload value,we refer to this formula :
1) IB ≤ In ≤ IZ
IB = Anticipated operating current of the circuit
IZ = Current carrying capacity of conductor or cable or Motor
In = Rated current of protective device
2) I2 ≤ 1,45 x IZ
Note:
IZ = Current carrying capacity of conductor or cable or Motor
For adjustable protective devices, In corresponds to the value set.
I2 = The current which causes tripping of the protective device under the conditions specified in the equipment regulations (high test current).
Common practice
Normally for overload relay setting depend on FLA ( Full Load Ampere ) of motor.We can see at the NAMEPLATE of motor.Normally setting for overload is 5% until 10 % more than FLA.
But it is depend on operation and functional of motor.For more detail setting,please refer manual guide of motor from manufacture.
We also can setting overload relay value depend on value of service factor motor.Example if service factor 1.15,we can setting 125% from FLA and if service factor is 1.0,we can setting 115% from FLA of motor.
Manual and automatic reset.
Normally,overload relay have this 2 reset function selection.We can choose manual or automatic reset after it trigger overload from motor.
I recommended for manual reset function because we can know when it trip and we can troubleshooting the root cause for tripping issue.So after we found the root cause,we can reset back the overload relay and can continue the operation.
hi sir,
I have one question about the relay settins in real time application. that is
While changing the relay setting in live air circuit breaker Have we switch off the breaker or no need?
I will give you one answer please check whether thwt is correct or not?
While increasing the relay setting of the air circuit breaker no need to switch off the circuit breaker.If we want to decrease the relay setting means we have to switch of the circuit breaker is it correct if this is wrongmeans plese give me correct idea and what is the actual reason and correct answer.
Regards
Gopalthulasidoss
plz send me all type of cntroling diagrams and explanation
thnks for giving this information to me
Are you idiot. ???
lol
Pleas send all tyep relly calculating chart
u guys are good thanks somuch
dear sir
what is formula of curve of overload protection class 10?
in circuit breaker siemens 3wn6173
Hey all,
I was wondering why my overload relay in an air compressor with a star delta starter is downsized compared to the motor fla?
Hi Jamie..
Your are compressor still running or always stop due to overload relay trip?
If air-compressor still running :-
1) check your overload relay condition.Perform test trip to ensure it is function properly,if not change it.
2) Check your Full Load Ampere using Clamp on meter for actual value and compare with your setting.
If your compressor always trip :-
1) Use your actual FLA value and make calculation and set a new setting for your overload relay.
Dear Sir
i would like to inform you i need electrical easy formula.or all electrical coculletion because my math matik is very week
1) druop volteg
2) callculetion of size of cable for equpment ( motol or etc)
3 from kva to mva 4) motor polarizetion 5) transformer steblity test
ETC…………
Hi Rajendratiwari,
In my blog,i already discuss about electrical calculation,Please find my post.I also create Electrical Formulas Categories for basic formula and calculation.
Please click link for Voltage drop and Cable sizing calculation.I hope it can help you to understand basic calculation.
hi sir ..
how do you now how much current drawn for 1hp motor ?
i want basic formula?
please tell m,e sir…
thanking you
i think the formula is
I= HP x 1.33
Dependo on voltage and losses
THIS FORMULA IS FOR SELECTION OF CABLE . FOR OVERLOAD RELAY THAT 5 TO 10% OF FLA OF MOTOR
Sir, please i need electrical calculation book for motors, overload e t c, because i want to know how to set overload for a motor
How to check the functionality of Over Load relay without connect the load (May be by control circuit testing)
Good question…It hard to tested of overload relay functioning without testing equipment like SIMOCODE pro from siemens.This process available only at Lab test.
Hai, I would like to ask,
I found a single line diagram, overload setting @ current/voltage module is 63A…630A.
Breaker is 250AF/250AT
Load is 15.75kW
****************************************************
My calculation: 15.75*1000/sqrt(3)/440V/0.8=25.8A
My question is
1) is the overload setting too high? should 25.8A within the overload setting? Can I say minimum value of overload setting cannot lower than 25.8A?
2) is the MCCB rating too high?current only 25.8A, but the breaker is 250AF?normally, we refer to which value, AF or AT (Because I have seen some stated 160AF/100AT)?why there is two AF and AT for MCCB?
Thank you
Dear sir
Am very pleased finding were we can share knowledge about electrical engineering .plis let me receive emails on the email above
Dear sir
i have a compressor having rating current 0.8A @220volt 5oHz. How can i calculate the overload protection for this compressor .
Hi,
You can used roughly calculation as per below example :-
Normally I set my overload protection around 115% to 120% from Full Load current.
For your application :
(0.8 x 120)/ 100 = 0.96 Ampere –> 1 Ampere
Thanks
Dear Sir,
Please solve my problem ,I want to run a three phase squirrel cage induction motor of 10 HP,415 volts rating by DOL Starter,Star Delta Starter and VFD(30Hz).
Please tell me the overload relay range and its setting,contactor rating,TPN MCB rating for backup fuse protection and cable size in each case.Sir,please give me the full calculation for this.I shall be highly thankfull for this.
With Regards,
Rajesh Kumar
Hello sir,
your motor kw : 7
full load amps : 12.98
you can set the relay range ; 13 A ( 8.9 A to 13.5 A )
Suitable MCB : C class 32 A
4 sq copper cable .1 sq copper cable can carry upto 5 A so its suitable to ur application..
1hp = 746..how come 10hp = 12 fla?
Yes, you are right..
Hello sir
My motor capacity is: 15Kw
Full load amps: 38A
So how can i set the relay range and suitable MCB ?
i have a three phase motor full load current [ name plate] 15 A @ 415v how can set over load relay please telme callculation
Hi
I want to know the exact setting of an electronic overload relay used on rigs ie type GL 90 main Motor rated current is 73amps service factor 1.15 voltage of 550 and 55kw running a 140cc hydraulic pump?
normal practice –> 15A x 110% = 16.5 AMP for overload relay setting
Very good info. Lucky me I recently found your blog by chance
(stumbleupon). I have book-marked it for later!
How setting for overload relay of motor formula.
Please send me.
wow its v usefull link
What does extra low voltage mean?
Extra low voltage is reduced voltage using transformer to 50 VDC or 120 VDC.Below from this voltage range we call extra low voltage.
The main purpose of Extra low voltage is to eliminate electrical shock.Equipment that located in swimming pool,public area or kindergarten normally used Extra low voltage.
This voltage also can be generate and synchronized with solar system and it green method to have electricity power supply.We also can reduce electricity consumption by using LED with Extra low voltage power supply.
Dear Sir,
i Recently got know about your blog , really pretty good,
i would like to know about Extra low voltage 50 or 120VDC in transformer, In this case Please provide details about How DC voltages used on transformer , is there coupling circuits , if you have circuit diagrams please send me,
Thanks
Jose..
Thanks you
I really like this website.
Keep it up.
Hi Sir,
Thanks for the compliment.
Feeling confident and well that this is the most interesting site that will really help.
Sir,
What is the overload setting for HV Motor of FLA= 303 @ 6.6V
Hi All,
Sir,
Help me please, our cable between softstater and overload relay keep burning out. exactly at outgoing to softstater. it is to control 3phase motor, 36A, 18.5kW at nameplate.
Softstater – Siemens 3RW3036 (22kW)
Overload.R. – Eaton ZB65-40
Dear sir I have 7.5 HP open wall moter at 300 volts power which relay can I use
Hello sir
Help me please,my overload relay for water pump system was repeatedly trip after a few minitus service.when I see the power draw beteween each phase,there is no difference.when I saw the load(currents) draw to the motor or submersible pump by clamp meter: on R-Phase 43A
on S- Phase 27A
on T- Phase 24A
there is some what difference,how can rearrengment this load( current) difference?
For information: motor,15KW
Voltage,380v or 400v,frequency 50Hz
length of the well (pump position 70m)
full load amps 38A
I want a well label diagram of a relay and it applications in electircal panels
Hello admin, i see your page needs fresh posts. Daily updates will rank your site in google higher, content is king nowadays. If you are to lazy to write unique posts everyday you should search in google for:
Ightsero’s Essential Tool
Dear sir
What is the meaning of the thermal overload method-curve&curve 46
what is the suitable relay for 15 hp star delta motor
I Know Power Factor Improvement Setting & Billi Meter Setting
sir my oueveshan is ht motor 3.3kv 2ookw my fault in in ht feeder in trip IN AMP. and I0 . INCRESE AND FEEDER TRIP
Dear Sir,
May I know how to calculate the tripping relay(mA) for RCCB.
In what condition I shall used 30mA or/and 100mA(tripping relay).
Thanks
Hi Tony Tan,
Please read my last post about RCCB –> http://www.electricneutron.com/circuit-breaker/residual-current-circuit-breaker/
55kw AC induction motor how to select overload relay and cont actor and breaker plz tell me
Hai sir,
You can set your overload relay at 105A and the Breaker size is 200A.
what is mean by “mA” value on MCB’s ??? how can we calculate this value
Milli ampher
I have a 45kw motor with a FLC of 86 A. It used to take 72A earlier but due to some changes done to process parameters is taking 93A for 10 seconds with a frequency of 2 times a minute. That means each phase of 93A there is a gap of 20 seconds and then the motor runs on full load. The MPCB has been kept at 80A but is not tripping yet. Is my motor safe, or do I need to change it to previous state?
Hi,
you can know your motor ampere limit at namplate.Please find service factor (SF) and times with motor FLA.That the ampere your motor can stand.
My opinion,if 93A is only for 20 sec,it still ok.I quest your starter is star delta right?what is your MCB ampere value?
I have 22kW 30HP motor so how can I cal.MCB rating ,ct rating, contactor size OL relay current setting .explain in detail by using formulae to cal. All parameters
how to select the OLR for 7.5kw feeder in DOL and START DELTA circut.
what can be the problem of this motor 19.5A, 415v.i ave installed 50A contactor,a phase failure and i ave set the overload at 22A.the motor has burnt twice what can be the problem.
Dear Sir,
Please tell me what check point of over load relay & MPCB before failure’s.
I found this website is very useful and each and everyone has their own answer that give us oppertunity to think further.Thru this website we all from diffrent country getting closer together.Thanks Guy.
keep it up
Overload setting formulae plz
which relay renge should be used with 30 hp sub motor with DOL starter
sir, how we find triping time of circuit breaker by using rely
I have a compressor rated at 230V 7.5HP FLA on the motor is 36 amps 60hz.
How to calculate to set the overload relay?
How do I know the amps of contactor and overload relay to use for, 2kw, 3kw, 5kw
Hi,Please find your equipment full load ampere or you can estimate with calculation.After that you can sizing your contactor and overload relay depend on FLA value..
Any body who ca help me……….?
how to draw thermal characteristics curve for specific induction motor.
Hi, after reading this awesome paragraph i am too
happy to share my experience here with friends.
What causes the over heating of over load?
pls advice
i had rewinding 3 phase motor 45kw,FLA 80A.After installation and test run about 12 hours the motor trip again .aftet check was found the motor winding already burnt.fyi overload setting is 95A.is it any possibility of this problem..
What is two metal use in bimetallic stip in thermal over load relay
I have enjoyed the good questions and corresponding answers to them thanks keep it up
DOL setting 5HP motor how mach ON Relay
me relay setting on 4 but motor taken current 8 trip
me relay setting on 4 but motor taken current 8amps trip
Hi sir
Good day
I am asking how can i calculate the Ir thermal setting for the circuit breaker to protect my motor
10 hp motor pump , at 415 volt 3 phase with 14 amp fla, what is the setting amp of the overload relay,,
14amps
Sir ..!
I have a question …plz tell me about refregration compressors and overloads how we can get the correct overload to set in compressor …when in overload not in compressor…plz
Pleas send all tyep relly calculating chart
good conversation about subject – if u have any particulor OLR setting chart please share
HOW TO SET THE OVERLOAD IF MOTOR FULL LOAD CURRENT IS 28.5AMS AND WHAT RANGE OF OVER LOAD SELECT
We have a 55kw motor with the rated current of 100 full load .If the overload setting is put at 75 ,just when the motor gets hot it trips coz we normally have poor voltage of 340 at peak.
But when set the overload setting up to 75 it delay to trip.what could be the problem?
Sir please send me formula of overload realy settings.
Full load current 71.5 amps, 440v, 60Hz, delta connection. What would be my thermal overload settings
45kw, 440v, 60hz motor. Delta connection, what would be my Full load current.